Toa VM-3360VA System Management Amplifier 360W for Commercial Use

- Estimated Delivery: 2–3 business days across the UAE
- Free Shipping & Returns : On all orders over AED 1000
The TOA VM3360VA CE is an efficient emergency voice evacuation and public address system, perfect for small to medium venues like shopping centers and schools. It features continuous speaker monitoring, built-in voice alarm, PA broadcasting, paging, and BGM functions, ensuring high audio quality and intelligibility. The system is easily installable, digitally processed, and offers versatile operation through front panel controls and PC software configuration.
Description
The TOA VM3360VA CE is a significantly cost-effective combined emergency voice evacuation alarm system and public address system. The VM-3360VA CE is particularly ideal for small to medium-sized applications, encompassing environments as varied as shopping centers, retail stores, nursing homes, schools, and fitness clubs. It integrates essential emergency voice alarm functions, including continuous speaker line monitoring and a built-in voice alarm. This user-friendly, all-in-one system additionally supports PA broadcasting, paging, and BGM functions, all of which maintain superior audio quality to ensure high intelligibility. The VM-3000 Series utilizes digital audio processing and control, with comprehensive digital audio mixing and an advanced electronic voice message feature. The setup may be efficiently carried out using the front panel controls and LCD display, which also facilitate simple system operation. Further enhancing operational versatility, the system includes dedicated software for configuration and setting updates via a PC.
Specifications
Power Source | AC mains, 50/60 Hz; DC: 24 V DC |
Power Consumption | 850W |
Rated Output | 360W |
Frequency Response | 50 – 20,000 Hz, ±3dB (at 1/3 rated output) |
Distortion | Under 0.8% (at rated output, 1kHz) |
Signal-to-Noise Ratio | Over 85dB |
Audio Input/Output Characteristic | Sampling frequency: 48kHz, A/D D/A Converter: 24bit |
Input | Input 1 – 3 : -50 dB (MIC)/-10dB (LINE) (changeable) 600Ω, electronically balanced combined XLR connector (female)/phone jack; Input 4: -50 dB (MIC)/-10 dB (LINE) (changeable) 600Ω, electronically balanced plug-in screw connector; BGM 1 – 2 : -10 dB, 10kΩ RCA pin jack; External AMP Input: 100V Line plug-in screw connector |
Output | Speaker output 1 – 2: max (360W) per output; Speaker output 3 – 6: max (120W) per output; Total within 360W plug-in screw connector; Direct output: Direct output from internal or external amplifier plug-in screw connector; Recording output BGM/Paging: 0dB, 10kΩ, RCA pin jack |
RM Link 1.2 in | 2 RJ45 female connectors for connecting the RM-300MF/RM-200M Remote Microphone. Maximum distance: RM1.2 Total 800 m; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
Network I/F | RJ45 female connector for switching hub or PC; 10 BASE-T/100 BASE-TX Circuit (Selectable by automatic negotiation); Maximum distance: 100m between this unit and a switching hub or PC; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
VM Link | RJ45 female connector for connecting the VM-3240E or VM-3360E; Maximum distance: 800m; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
EXT PA Link | RJ45 female connector for connecting the VP-2241 or VP-2421; Maximum distance: 5m; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
General Control In: 1 – 8, Out: 1 – 8 | Plug-in screw connector; Input: No-Voltage make contact input, open voltage: 24V DC, short-circuit current: under 1 mA; Output: Isolated open collector output, withstand voltage: 30V DC, operating current: under 50 mA |
Emergency Control In: 1 – 6, Status out | RJ45 female connector; Input 1 – 5: No-Voltage make contact input, open voltage: 24V DC, short-circuit current: under 2 mA; Connection resistance to make the function: Inactive: 9.4kΩ ±5%, Active: 4.7kΩ ±5%; Input 6: Isolated voltage input: Inactive: -24V ±20%, Active: +24V ±20%; Status out: Relay contact output, withstand voltage: 40V DC, operating current: 2 – 300mA |
ATT Control | Plug-in connector, relay contact, 30V DC, 125V AC 5A (AC/DC) |
Power In/Out PS Out, DC Power In | M4 Screw terminal, distance between barriers 11 mm; This connector is for connecting the VX-2000DS only; DC 28V/30A (operating range: 20 – 40V DC) |
DC24V Output | 24V DC ±10%, Maximum feeding current 0.4A |
DS Link | RJ45 female connector for connecting the VX-2000DS; Maximum distance: 5m; Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP) |
Dimensions | 482 (W) x 132.6 (H) x 460 (D)mm |
Weight | 19kg |
Option | Input transformer: IT-450 |
Additional information
Brand |
---|